Points Relating to Steam Heating.
No two pipes should discharge into a T from opposite directions, thus retarding the motion of both or one of the returning currents. This is called “butting” and is one of the most vexatious things to encounter in pipe fitting.
Fig. 131.
Fig. 132.
Fig. 133.
All steam piped rooms should be frequently dusted, cleaned and kept free from accumulation of inflammable material.
The use of the air valve is as follows: In generating steam from cold water all the free air is liberated and driven off into the pipe, with the air left in them, all of which is forced up to the highest point of the coils or radiators, and compressed equal to the steam pressure following it. Now, by placing a valve or vent at the return end of the pieces to be heated, the air will be driven out by the compression. Why the vent is placed at the return is, that the momentum of the steam, it being the lightest body, will pass in the direction of it, falling down into the return as it condenses, thus liberating the air. Otherwise, should the vent not work, and the air is left in the radiator, it will act as an air spring, and the contents of the pipes left stationary will be the result; no circulation, no heat; and the greater steam pressure put on, the greater the chances are of not getting any heat; and thus a little device, with an opening no larger than a fine needle, will start what a ton of pressure would not do in its absence.
If the drip and supply pipes are large there is very little danger of freezing, provided suitable precautions are taken to leave the pipes clear. They should be blown through, when left, and the steam valve should be closed. There should also be a free chance for air to escape in all systems of piping.
No rule can be given relating to capacity for heating pipes and radiators which do not require to be largely modified by surroundings.
The field of steam heating would seem to be limitless—in one public building it required recently 480,000 dollars to meet the expenditures in this single line. As an example of warming on an extensive scale may be taken a large office in New York, of which the following are the particulars:
| Total number of rooms, including halls and vaults. | 286 | |
| Total area of floor surface. | sq. ft. | 137,370 |
| Total volume of rooms. | cub. ft. | 1,923,590 |
A second example is furnished by the State Lunatic Asylum at Indianapolis:
| Length of frontage of building, more than. | 2,000 lin. ft. | |||
| Total volume of rooms. | 2,574,084 cub. ft. | |||
| Warming Apparatus | indirect radiating surface | 23,296 | ||
| Direct | 10,804 | |||
| Total | 34,100 sq. ft. | |||
| Boilers | Grate area | 180 sq. ft. | ||
| Heating surface | 5,863 sq. ft. | |||
The “overhead” system of heating with steam pipes has several advantages. 1. The pipes are entirely out of the way 2. They do not become covered with odds and ends of unused materials. 3. If they leak the drip fixes the exact location of place needed to be repaired. 4. The room occupied overhead cannot be well otherwise utilized, hence in shops the system has proved efficient.
But for offices or store rooms the overhead system is not approved of owing to the heat beating down upon the occupants and causing headache.
When overhead heating pipes are used, they should not be hung too near the ceiling. If the room be a high one, it is better to hang them below, rather than above, the level of the belts running across the room, and they should not be less than three or four feet from the wall.
Fig. 134.
It is important to protect all wood work or other inflammable material around steam pipes from immediate contact with them, especially where pipes pass through floors and partitions. A metal thimble should be placed around the steam pipe, and firmly fastened on both sides of the floor, in such a way as to leave an air space around the steam pipe.
For indirect radiating surfaces, the box coils are the forms most used. The chambers or casings for containing them are made either of brickwork, or often of galvanized sheet-iron of No. 26 gauge, with folded joints. The coils are suspended freely within the chambers, which are themselves attached to the walls containing the air inlet flues. Besides coils of wrought iron tubes, cast-iron tablets or hollow slabs, having vertical surfaces with projecting studs or ribs, have been extensively used for the radiating surfaces.
As the amount of heat given off from the radiator cannot be satisfactorily controlled by throttling the steam supply, it is usual to divide all radiators into sections, each of which can be shut off from the supply and return mains, separately from the rest of the sections. This method of regulation applies to radiators for indirect heating as well as for direct.
Vertical pipe coils, constitute a distinctive form of radiator now largely used. In these a number of short upright 1-inch tubes, from two feet 8 inches to 2 feet 10 inches long, are screwed into a hollow cast iron base or box; and are either connected together in pairs by return-bends at their upper ends, or else each tube stands singly with its upper end closed, and having a hoop iron partition extending up inside it from the bottom to nearly the top. The supply of steam is admitted into the bottom casting; and the steam on entering, being lighter than the air, ascends through one leg of each siphon pipe and descends through the other, while the condensed water trickles down either leg, and with it the displaced air sinks also into the bottom box. For getting rid of the air, a trap is provided, having an outlet controlled by metallic rods; as soon as all the air has escaped and the rods become heated by the presence of unmixed steam, their expansion closes the outlet.
A thorough drainage of steam pipes will effectually prevent cracking and pounding noises.
The windward side of buildings require more radiating surface than does the sheltered side.
When floor radiators are used, their location should be determined by circumstances; the best situations are usually near the walls of the room, in front of the windows. The cold air, which always creates an indraft around the window frames, is thus, to some extent, warmed as it passes over the the radiators, and also assists in the general circulation.
Water of condensation will freeze quicker than water that has not been evaporated, for the reason that it has parted with all its air and is therefore solid.
Whatever the size of the circulating pipes, the supply and drip pipes should be large, to insure good circulation; the drip pipes especially so. This is also the more necessary when the pipes are exposed, or when there is danger of freezing after the steam is shut off.
It is important to see that no blisters or ragged pipes go into the returns, and also to make sure that the ends are not “burred in” with a dull pipe cutter wheel so as to form a place of lodgment for loose matter in the pipe to stop against.
Figs. 135-137.
Experiments recently made on the strength of bent pipes have developed some things not commonly known, or at least not recognized, that is, the strain on the inside of the angles, due to the effort of the pipes to straighten themselves under pressure. The problem is one of considerable intricacy, resolvable, however, by computation, and is a good one for practice. In the experiment referred to, a copper pipe of 63⁄4 in. bore, 3⁄16 in. thick, was used. The angle was 90 degrees, and the legs about 16 in. long from the center. At a pressure of 912 pounds to an inch, the deflection of the pipe was nearly 3⁄8 in., showing an enormous strain on the inner side, in addition to the pressure.
Steam valves should be connected in such a manner that the valve closes against the constant steam pressure.
Interesting experiments show that the loss by condensation in carrying steam one mile is 5 per cent. of the capacity of the main, and a steam pressure of seventy-five pounds carried in five miles of mains, ending at a point one-half mile from the boiler house only shows a loss of pressure of two pounds.
In steam warming it is necessary to bring the water to a boiling point to get any heat whatever; in hot water warming, a low temperature will radiate a corresponding amount of heat.
Never use a valve in putting in a low pressure apparatus if it is possible to get along without it. All the valves or cocks that are actually required in a well-proportioned low pressure apparatus are, a cock to blow off the water and clean out the return pipes, another to turn on the feed water. Of course the safety valves, gauge cocks, and those to shut fire regulators and such as are a part of the boiler, are not included in this “point.”
The most important thing in connecting the relief to return pipes is, that it should always be carried down below the line, the same as all vertical return pipes. In connecting the reliefs, so that the lower opening can at any time be exposed to the steam, there will be the difficulty of having the steam going in one direction, and the water in another.
The relief pipe should “tap” the steam at its lowest or most depressed points. It should always be put in at the base of all steam “risers” taking steam to upper floors.
In leaving the boiler with main steam pipe, raise to a height that will allow of one inch fall from the boiler to every ten feet of running steam pipe; this is sufficient, and a greater fall or pitch will cause the condensed water in the pipe to make at times a disagreeable noise or “gurgling.”
The flow pipe should never start from the boiler in a horizontal direction, as this will cause delay and trouble in the circulation. This pipe should always start in a vertical direction, even if it has to proceed horizontally within a short distance from the boiler. Reflection will show that the perfect apparatus is one that carries the flow pipe in a direct vertical line to the cylinder or tank; this is never, or but rarely possible, but skill and ingenuity should be exercised to carry the pipes as nearly as possible in this direction.
The flow of steam ought not to be fast enough to prevent the water of condensation from returning freely. All the circulating pipes should be lowest at the discharge end, and the inclination given them should not be less than one foot in fifty.
Fig. 138.
Fig. 139.
Fig. 140.
Fig. 141.
The general rule is to lay the main pipes from the boiler so that the pipe will drain from the boiler. Where this is done it is necessary to have a drip just before the steam enters the circulation. This drip is connected to a trap, or, if the condensed water is returned to the boiler, the drip is arranged accordingly.
But it is the best practice to lay the main pipe with the lowest part at the boiler, so that the drip will take care of itself, and not require an extra trap, nor interfere with the return circulation.
When steam is turned into cold pipes the water of condensation gets cold after running a short distance, and if it has to go through a small drip pipe full of frost it will probably be frozen. Then, unless it is followed up with a pail of hot water, the whole arrangement will be frozen and a great many bursted pipes will result. Whenever turning steam on in a system of very cold pipes, only one room should be taken at a time, and a pail of hot water should be handy so that if the pipe becomes obstructed it can be thawed immediately without damage.
When pipes become extensively frozen there is nothing to do but take them out and put in new ones.
Fig. 142.
Fig. 143.
The manner in which a temperature too low to start rapid combustion in wood in steam pipes, operates in originating a fire is by first reducing the oxide of iron (rust) to a metallic condition. This is possible only under certain external conditions, among them a dry atmosphere. Just as soon as the air is recharged with moisture, the reduced iron is liable to regain, at a bound, its lost oxygen, and in doing so become red hot. This is the heat that sets the already tindered wood or paper ablaze.
Where there is no rust there is no danger from fire with a less than scorching temperature in the pipe or flue. Hence the necessity of keeping steam or hot water fittings in good order.
The indirect system of heating is the most expensive to put in; as to the cost of providing nearly double the heating surface in the coils must be added the cost of suitable air boxes, pipes and registers. For a large installation, this is a serious matter, although for office warming the advantages gained on the score of healthfulness and greater efficiency of employees much more than counterbalance the extra expense.
One horse power of boiler will approximately heat 6,000 to 10,000 cubic feet in shops, mills and factories—dwellings require only one horse power for from 10,000 to 20,000 cubic feet.
From seven to ten square feet of radiating surface can be heated from one square foot of boiler surface, i.e., the heating surface of the boiler and each horse power of boiler will heat 240 to 360 feet of 1-inch pipe.
The profession most nearly related to that of steam engineers is the working steam fitters’ occupation. Strictly speaking, the engineer should produce the steam, and it is the steam fitters’ place to fix up all the steam pipes and make all the necessary connections: but where the steam plants are small, the engineer may be steam fitter also: hence the introduction in this work of these “Points” which are necessary to be known for the proper care and management of any system of steam or hot water heating.
The care and patience, the mental strain and not infrequently the physical torture incident to fitting up a complicated pipe system cannot adequately be set forth in words.
It is stated to be a fact, that in high pressure hot water heating the water frequently becomes red hot, pressures of 1000 to 1200 pounds per square inch being reached, and when the circulation of the system is defective the pipe becomes visibly red in the dark.
Pipes under work benches should be avoided, unless there is an opening at the back to permit the escape of the heated air, which would otherwise come out at the front.
When both exhaust and live steam are used for heating, many engineers prefer to use independent lines of pipe for each, rather than run the risk of interference and waste caused by admitting exhaust and live steam into the same system at the same time. Nevertheless, the advantages gained by being able to increase the heating power of a system in extremely cold weather by utilizing the entire radiating surface for high pressure steam, are so great that it is probably better so to arrange the system of pipes and connections that this can be done.
Double extra heavy pipe (XX) is used for ice and refrigerating machines (see page [246]), as a general rule, makers of this class of machinery obtain but little satisfaction in the use of the ordinary thread joining and use special dies with uniform taper—both for couplings, flanges and threading the pipe itself. They do this to protect their reputation and guarantees.
Welding boiler and other tubes.—The following is a good way in cases of emergency and can be done on a common forge:
Enlarge one end of the shortest piece, and one end of the long piece make smaller, then telescope the two about 3⁄4 of an inch. Next get an iron shaft as large as will go into the tube and lay across the forge with the tube slipped over it. Block the shaft up so that the tube will hang down from the top of the shaft. By such an arrangement the inside of the tube will be smooth for a scraper. When the tube gets to a welding heat strike on the end of the short piece first, with a heavy hammer, then with a light and broad-faced hammer make the weld. Borax can be used to good advantage, but it is not necessary. The next thing is to test the tube, which can be done in the following manner: Drive a plug in one end of the tube, stand it up on that end, and fill it with water, if it does not leak the job is well done, if a leak exists the welding must be again done.
Solid-drawn Iron Tubes: Calculated Bursting and Collapsing Pressures.
| External Diameter. | Thickness. | Internal Diameter. | Bursting Pressure. | Collapsing Pressure. | ||
|---|---|---|---|---|---|---|
| Per Square Inch of Internal Surface. | Per Square Inch of Section of Metal. | Per Square Inch of External Surface. | Per Square Inch of Section of Metal. | |||
| Inches. | Inch. | Inches. | Lbs. | Tons. | Lbs. | Tons. |
| 11⁄4 | .083 | 1.084 | 7700 | 22.4 | 6500 | 21.7 |
| 13⁄8 | .083 | 1.209 | 6900 | 22.4 | 5800 | 21.3 |
| 11⁄2 | .083 | 1.334 | 6200 | 22.4 | 5200 | 21.0 |
| 13⁄4 | .083 | 1.584 | 5300 | 22.4 | 4300 | 20.3 |
| 2 | .083 | 1.834 | 4500 | 22.4 | 3700 | 19.7 |
| 21⁄4 | .095 | 2.060 | 4600 | 22.4 | 3600 | 19.0 |
| 21⁄2 | .109 | 2.282 | 4800 | 22.4 | 3600 | 18.3 |
| 23⁄4 | .109 | 2.532 | 4400 | 22.4 | 3100 | 17.7 |
| 3 | .120 | 2.760 | 4300 | 22.4 | 3000 | 17.0 |
| 31⁄2 | .134 | 3.232 | 4200 | 22.4 | 2700 | 15.7 |
| 33⁄4 | .134 | 3.482 | 3900 | 22.4 | 2400 | 15.0 |
| 4 | .134 | 3.732 | 3600 | 22.4 | 2100 | 14.3 |
| 41⁄2 | .134 | 4.232 | 3200 | 22.4 | 1700 | 13.0 |
| 43⁄4 | .134 | 4.482 | 3000 | 22.4 | 1600 | 12.3 |
| 5 | .134 | 4.732 | 2800 | 22.4 | 1400 | 11.7 |
| 51⁄2 | .148 | 5.204 | 2800 | 22.4 | 1200 | 10.3 |
| 6 | 5.704 | 2600 | 22.4 | 1000 | 9.0 | |