4 killed, 3 injured.

Fig. 25.

Breeches tube 25ft. 6in. long, 7ft. 6in. diameter, plates 7/16 inch, pressure 30 lbs. Front end and fire-grate tubes and taper junction were thrown to the front in one piece. Main shell not injured. Back part of tube remained in boiler. Bottom part of taper junction where flattened to receive the two fire tubes, collapsed upwards. The cause of explosion was the want of proper stays or strengthening tubes, and consequent weakness. There was only one safety valve of small size.

No.41. Chippenham. ([Fig. 26.])

November 21st.

3 killed, 2 injured.

Fig. 26.

One tube Cornish, 11ft. long, 5ft. diameter, pressure 44 lbs. Tube gave way at an old crack at back of strap-plate and partially collapsed.