Fig. 1.

One of five. Cornish, 13 years old, 30ft. long, 6ft. 6in. diameter. Tube 3ft. 3in. diameter, 3/8 inch plates, 30 lbs. pressure. Tube collapsed sideways from weakness, and the front part and the front plate were blown out, carrying the attendants into a deep and swollen river which ran close in front of boilers.

No.2. South Wales. ([Fig. 2.])

January 15th.

1 killed, 4 injured.

Fig. 2.

Plain cylinder, very old, 32ft. long, 5ft. diameter, 7/16 inch plates, 30 lbs. pressure. Externally corroded to 1/16 inch, and gave way near a seam, the front being thrown forward into a house, and the back end 150 yards to the rear, carrying away the stack. It had been badly repaired with bolted patches which had hastened corrosion, and as it was known to be nearly worn out, it was to have been replaced in a few days.

No.3. Worksop. ([Fig. 3.])

January 28th.