1 killed, 2 injured.

Fig. 25.

Lancashire, 26ft. long, 6ft. 6in. diameter. Tubes 2ft. 9in. diameter, 3/8 inch plates, 60 lbs. pressure. The left hand tube collapsed from overheating through shortness of water, and the contents issued violently and scalded those near.

No.43. Hereford.

August.

2 injured.

Chemical boiler, Plain cylinder, 12ft. 6in. high, 4ft. 6in. diameter, 3/8 inch plates, with cast-iron hemispherical ends with manhole in each. The pressure of 34 lbs. was obtained from another boiler. The bottom end gave way where the casting was defective, a piece was blown out, and the reaction of the issuing contents projected the boiler through the roof, through which it again descended and did much damage.

No.44. Cardiff. ([Fig. 26.])

September 1st.