The neat cement briquette tests showed that those immersed in sea-water attained a high degree of strength at a much quicker rate than those immersed in fresh water, but the 1 to 3 cement and sand briquette tests gave an opposite result. At the end of twelve months, however, practically all the cements set in fresh water showed greater strength than those set in sea- water. When briquettes which have been immersed in fresh water and have thoroughly hardened are broken, the cores are found to be quite dry, and if briquettes immersed in sea-water show a similar dryness there need be no hesitation in using the cement; but if, on the other hand, the briquette shows that the sea-water has permeated to the interior, the cement will lose strength by rotting until it has no cohesion at all. It must be remembered that it is only necessary for the water to penetrate to a depth of 1/2 in on each side of a briquette to render it damp all through, whereas in practical work, if the water only penetrated to the same depth, very little ill-effect would be experienced, although by successive removals of a skin 1/2 in deep the structure might in time be imperilled.

The average strength in pounds per square inch of six different well-known brands of cement tested by Mr. O'Hara was as follows:—

TABLE No. 16.

EFFECT OF SEA WATER ON STRENGTH OF CEMENT.

Neat cement 1 cement to 3 sand
set in set in
Sea Water Fresh Water Sea Water Fresh Water

7 days 682 548 214 224
28 days 836 643 293 319
2 months 913 668 313 359
3 months 861 667 301 387
6 months 634 654 309 428
9 months 542 687 317 417
12 months 372 706 325 432

Some tests were also made by Messrs. Westinghouse, Church, Kerr, and Co., of New York, to ascertain the effect of sea- water on the tensile strength of cement mortar. Three sets of briquettes were made, having a minimum section of one square inch. The first were mixed with fresh water and kept in fresh water; the second were mixed with fresh water, but kept immersed in pans containing salt water; while the third were mixed with sea-water and kept in sea-water. In the experiments the proportion of cement and sand varied from 1 to 1 to 1 to 6. The results of the tests on the stronger mixtures are shown in Fig. 32.

The Scandinavian Portland cement manufacturers have in hand tests on cubes of cement mortar and cement concrete, which were started in 1896, and are to extend over a period of twenty years. A report upon the tests of the first ten years was submitted at the end of 1909 to the International Association of Testing Materials at Copenhagen, and particulars of them are published in "Cement and Sea-Water," by A. Poulsen (chairman of the committee), J. Jorsen and Co., Copenhagen, 1909, price 3s.

[Illustration: FIG. 32.—Tests of the Tensile Strength of
Cement and Sand Briquettes, Showing the Effect of Sea Water.]

Cements from representative firms in different countries were obtained for use in making the blocks, which had coloured glass beads and coloured crushed glass incorporated to facilitate identification. Each block of concrete was provided with a number plate and a lifting bolt, and was kept moist for one month before being placed in position. The sand and gravel were obtained from the beach on the west coast of Jutland. The mortar blocks were mixed in the proportion of 1 to 1, 1 to 2, and 1 to 3, and were placed in various positions, some between high and low water, so as to be exposed twice in every twenty- four hours, and others below low water, so as to be always submerged. The blocks were also deposited under these conditions in various localities, the mortar ones being placed at Esbjerb at the south of Denmark, at Vardo in the Arctic Ocean, and at Degerhamm on the Baltic, where the water is only one-seventh as salt as the North Sea, while the concrete blocks were built up in the form of a breakwater or groyne at Thyboron on the west coast of Jutland. At intervals of three, six, and twelve months, and two, four, six, ten, and twenty years, some of the blocks have, or will be, taken up and subjected to chemical tests, the material being also examined to ascertain the effect of exposure upon them. The blocks tested at intervals of less than one year after being placed in position gave very variable results, and the tests were not of much value.