Table 1.—Determining tile-disposal field requirements from percolation tests[6]

Minutes required for water to fall 1 inchEffective absorption area required, per person, in bottom of disposal trenchesMinutes required for water to fall 1 inchEffective absorption area required, per person, in bottom of disposal trenches
Square feetSquare feet
2 or less261052
3301563
4363090
54060[7]120

[6] A minimum of 150 square feet should be provided, equal to 100 feet of 18-inch trench.

[7] If more than 60 minutes, use special design with seepage pits or sand-filter trenches.

Figure 9 suggests methods of arranging the tiles in disposal fields under varying conditions and the length of tiles needed.

DISPOSAL-TILE TRENCH

Disposal-tile lines—Maximum length for each line 100 feet. All lines to be equal in length.
Disposal-tile lines to slope 2" to 4" per 100 feet, not over 6". Sewer-tile lines to slope 1/8" to 1/4" per foot.

SIZE AND MINIMUM SPACING REQUIREMENTS
FOR DISPOSAL TRENCHES
TRENCH WIDTH-W IN INCHESTRENCH DEPTH-D IN INCHESEFFECTIVE ABSORPTION AREA IN SQUARE FEET PER LINEAL FOOTTILE LINES SPACING-S IN FEET
1818 to 301.56.0
2418 to 302.06.0
3018 to 362.57.5
3624 to 363.09.0
Wider spacing of the lines desirable where
available area permits

Figure 9.—Arrangements for tile-disposal fields, method of laying tile, and length of tiles needed.

DISPOSAL METHODS IN TIGHT OR WET SOILS

If the soil is heavy clay or has tight formation, yet shows some porosity from percolation tests, the efficiency of the field may be increased by placing below the tile lines 12 to 15 inches of additional filter material (washed gravel, crushed stone, slag, clean cinders, or clean bank-run gravel 3/4 to 21/2 inches in size). When the surface soil is tight and is underlain by porous soil, sufficient drainage is sometimes obtained for the smaller installations by omitting the tile field and providing a dry well at the end of the effluent sewer, provided the water table will not be contaminated. Larger systems under such soil conditions should have a tile field, and absorption can be increased by boring 6- or 8-inch holes down to the porous stratum and filling them with gravel or sand; the holes should be 4 to 6 feet apart. Another and perhaps the best practice is to excavate the tile trenches 4 to 6 feet and install a lower tile line, as shown in [figure 10]. This latter method is especially desirable if the upper tight stratum is especially thick, or if there is no porous lower stratum, or if in irrigated regions and where the disposal field is limited in area.