No.Name.Steam at
Beginning.
Steam
during
Work.
Time of
filling
Tank.
' "
1Shand & Mason100 3 0
2Butt & Co.100 3 3
3Merryweather & Son145 3 7
4Roberts80 12 30

Roberts did not fill the tank.

THIRD TRIAL.

Delivering into large tank at a horizontal distance of 40 feet, a vertical height of 40 feet, a true distance of 56 feet, and at an angle of 45 degrees from the horizon, the depth from which water was drawn being 16 feet 4 inches.

Key:
A — No. of Deliveries Open.
B — Length of Hose.
C — Average Steam Pressure.
D — Average Water Pressure.
E — No. of Gallons Delivered.

No.Name. Time. A BSize of
Nozzle.
C D E Time of
Raising
Steam.
hr. m. s.
1 Merryweather
& Son
1 24 55 2 440 1-1/2 91 89 16,086 10' 32"
to
80lbs.
2 Shand
& Mason
2 0 0 2 440 1-1/2 &
1-3/8
96 62 12,917 11' 21"
to
120lbs.
3 Roberts 2 0 0 1 420 1-1/4 75 75 9,936 11' 20"
to
80lbs.
4 Butt & Co. 0 46 50 2 440 1-1/2 78 78 8,280 14' 10"
to
45lbs.
5 Easton &
& Amos
1 32 35 2 440 1-3/8 98 41 3,036 12' 30"
to
90lbs.
6 Nichols
(Manhattan)
0 4 55 2 420 1-1/2 None. 13' 09"
to
45lbs.

Merryweather and Son—Fire lighted at 4h. 1m. 55s.; gauge moved at 4h. 8m. 20s.; engine started at 4h. 12m. 27s.; water drawn in about 10 revolutions; pumps not primed, valve box leaked slightly, and engine worked satisfactorily in every respect.

Shand and Mason—Fire lighted at 11h. 25m. 46s.; gauge moved at 11h. 32m. 53s.; engine started at 11h. 37m. 7s.; pump primed at 11h. 45m. 48s.; drew water at 11h. 47m.; water first through the nozzle at 11h. 48m. 59s.; in hood at 11h. 49m. 19s.; shifted nozzle (3-1/4m. delay); high wind.

Roberts—Fire lighted at 11h. 17m.; engine, started at 11h. 28m. 20s.