23a. The guaranteed efficiency of motor shall not be less than 78% at half load and not less than 84% at full load.

24 to 32. Same as for Class 1.

32a. Motor shall be subject to shop test to determine efficiency, heating, insulation, etc. Manufacturers’ certified test sheets of motor, giving all readings taken during shop test, together with calculated results, must be submitted to the Architect for approval before motor is shipped from factory.

33. Rheostat. Furnish and install where shown, upon a slate panel hereinafter specified, a starting rheostat of proper size and approved make, designed for the particular duty it has to perform. It must have an automatic no-voltage and overload release. All resistance for rheostat is to be placed on the back of the tablet. Contacts must project through board to front side. All moving parts must be on front of board.

33a. Tablet. Furnish and place where shown, a slate tablet not less than ³⁄₄ in. thick, supported by a substantial angle iron frame, so placed that there will be a space of not less than 4 in. between the wall and back of resistance. Mount on this tablet one double-pole, 250-volt knife switch, with two 250-volt inclosed fuses and one starting rheostat, as specified hereinbefore. The connections shall be on the back of the tablet. The space between the column and the tablet shall be enclosed with a removable diamond-mesh grill of No. 10 wire in channel frame.

34, 35 and 36. Same as for Class 1.

36a. Automatic Control. Suitable means shall be provided in connection with the rotary exhauster that will maintain the vacuum in the separators within the limit of the machine at point found to be most desirable, irrespective of the number of sweepers in operation.

36b. Controller shall consist of a suitable means provided in the exhauster, or as an attachment thereto, which will automatically throw the exhauster out of action by admitting atmospheric pressure to the exhauster only, but not to the system; whenever the vacuum in the separator rises above the point considered desirable, and throw the exhauster into action when the vacuum falls below the established lower limit.

36c. In addition to control, a positive vacuum breaker having an opening equal to 1 in. diameter pipe net for 6 in. of mercury, must be provided on separator.

36d. If centrifugal fan is used, no control or vacuum breaker will be required.