When two or more generators are used, it is necessary to provide means to prevent the current from dividing unequally between them; if this were not done, one machine might do nearly all the work, while the other one would be practically idle. The means employed to accomplish the result is simply an additional bus bar, which is called an equalizing bus. We will not undertake to explain the principle upon which this arrangement acts; it is sufficient to say that by such means the work can be distributed in amounts directly proportional to the capacity of the generators, so that if one machine is very much larger than the others it will take a portion of the load corresponding to its size. In order that these results may be attained it is necessary to properly adjust the several generators, and as no machine can be made to work with the accuracy of perfection, the work will not be distributed in true proportion for all conditions of load; thus if the generators are adjusted so as to each take its proper share when all the cars are in operation, one machine may do too much or not enough when only one half the number are running, but the excess or deficiency will not be more than a few per cent unless the adjustment is very defective.

Electric generators for railway work are made in all sizes, from those only large enough to operate four or five cars to others capable of furnishing sufficient current for thirty or forty or even more. Small generators are made so as to be driven by a belt running over a pulley mounted on the end of the armature shaft, or they may be arranged to be connected to the end of a steam-engine shaft, and thus become what is called direct connected machines. Large generators are almost invariably of the latter type. A machine of this class is illustrated in [Fig. 23]. The driving engine is shown at E, the cylinder being in the background and the crank toward the front, the shaft being clearly seen at S, while F is the fly wheel. The generator is mounted directly upon the engine shaft, between the bearing at the crank end and the fly wheel. The large ring marked G is the field magnet ring, and at D D D the field coils are shown. These coils are equally spaced all the way around the circle. The commutator is marked C, and the commutator brushes are located at B B. The armature can not be seen very well, as it is covered by the brush holders and their supporting frames, but it is located within the ring G in the position designated by A. This machine is one of a number used to operate the roads of Troy, N. Y., and is of about one-thousand-horsepower capacity, which is enough to furnish all the current required to run sixty or seventy cars.

Fig. 23.—Large-Size Direct connected Electric Railway Generator.

The switches a a and b b, shown in [Fig. 22], and the bus bars A B, are mounted upon a large panel, made of marble or slate, called a switch board. These switches are sufficient for the purpose of turning the current on or off any track or for connecting and disconnecting the generators, but for the successful operation of the plant it is necessary to have other devices by means of which the strength of the current may be ascertained, and also the electro-motive force. It is necessary to provide each generator with means for varying the electro-motive force of the current it generates, otherwise the load could not be properly equalized between the several machines. All these different devices are located upon the switch board, so as to have them in an accessible position. A railway switch board, arranged for four generators and a large number of distributing circuits, is shown in [Fig. 24]. The four generator switches are shown at a a a a, and the circles marked R, directly under them, are the devices by means of which the electro-motive force of the current is regulated. These devices are called field regulators, from the fact that their office is to regulate the strength of the field magnets of the generators, making them stronger to increase the electro-motive force and weaker to reduce it. The part seen upon the front of the switch board is not the regulator proper, but only the handle and the contact points over which this swings. The instruments marked A A A A are for measuring the strength of the current of each individual generator, and are called ammeters. The instruments marked V V V V are for the purpose of indicating the electro-motive force of the currents of the several generators, and are called voltmeters. Ag is an ammeter used to measure the strength of the total current, and Vg is a voltmeter that indicates the electro-motive force of the current passing out to the cars on the various lines. The ammeter Ag is not an actual necessity, for the strength of the total current can be ascertained by adding the readings of the four instruments connected with the generators, but it is a convenience, as it saves the trouble of performing the addition. The voltmeter Vg, however, can not be regarded in this light; in fact, its presence is decidedly serviceable, for it indicates the average electro-motive force of all the generators; therefore if any one of the instruments V V V V is higher or lower it shows at once that the generator to which it is attached is out of adjustment and not doing its proper share of the work. The switches b b b, by means of which the current is turned on to the several external circuits, are shown at the extreme end of the switch board.

The instrument marked W, located between the a switches, is called a wattmeter, and its office is to indicate the amount of power furnished by the generators. This instrument is not always used, as it is a convenience but not a necessity. It can be seen at once that whether it is used or not, the amount of power required to operate the roads will be the same, but it is thought by most railroad managers that it is desirable, for then the relation between the coal consumed and the power developed can be seen; and if the showing is not as good as it should be, the engineer can remind the firemen that they are not exercising as much care in feeding the boilers as they should. Considered in this light, the watt-meter acts as a check to wastefulness on the part of the employees.

Fig. 24.—Electric Railway Switchboard.

The instruments marked C C C C serve the same purpose in connection with the generators as the safety fuses do with respect to the car motors; they are electro-magnetic devices used to open the generator circuits whenever the current reaches a strength that is sufficient to injure the machine. These devices are called circuit breakers. As will be noticed, there are four located directly above the four a switches, and, at the farther end of the board, a large number located directly above the b switches. The latter act to open the individual circuits when the currents flowing in them become too strong, and the former are controlled entirely by the current of the generator circuits. A circuit breaker is more reliable than a safety fuse, because it acts quicker. With the fuse the current must act for some time before it can melt the metal, as a sufficient amount of heat can not be generated instantly. With the circuit breaker, however, the action is instantaneous, for as soon as the current reaches the predetermined strength the magnetism of the operative parts of the device becomes sufficiently strong to cause it to act. A circuit breaker is simply a switch that is arranged to be opened automatically by the action of a magnet, instead of by the hand of the operator. The switch part of the apparatus is held in place by a catch that is set much after the fashion of the catch in a mouse trap—that is, so that the least pressure will disengage it. A strong spring acts to throw the switch open, and as soon as the catch is tripped by the actuating magnet the force of the spring comes into action and the circuit is opened.

The circuit breaker is a very valuable apparatus, for it frequently happens that, through delays of one kind or another, a large number of cars concentrate at one point on the road, and, as all the motormen are anxious to make headway, they all start up at once at the first opportunity. If there were no circuit breakers at the power house the result would be that some of the generators would be greatly overloaded and perhaps disabled; but, owing to the presence of the circuit breakers, the actual result is that the circuit is broken, and then the motormen have to wait until the current is turned on again. If too many of them try to start their cars at the second trial the current will again stop. After two or three ineffectual efforts have been made to start all the cars together the motormen will conclude to go easy, and set a few in motion at a time. In this way the cars will become more evenly distributed along the line, and the demand for current at the point of blockade will reduce to the normal amount, or nearly so, and the running of the cars will continue without further interruption, for the current drawn by the motors having been reduced to the average amount, the circuit breaker will cease to act.