Strand Theater,10 P.M.,gallery0.101partsCO2per 100.
Surrey Theater,10 P.M.,boxes0.126"""
Surrey Theater,12 P.M.,boxes0.218"""
Olympia Theater,11.30 P.M.,boxes0.082"""
Olympia Theater,11.55 P.M.,boxes0.101"""
Victoria Theater,10 P.M.,boxes0.126"""
Haymarket Theater,10 P.M.,boxes0.076"""
City of London Theater,11.15 P.M.,pit0.252"""
Standard Theater,11 P.M.,pit0.320"""
Theater Royal, Manchester, pit0.2734"""
Theater Royal, Manchester, pit0.2734"""
Grand Theater, Leeds, pit0.150"""
Grand Theater, Leeds, upper circle0.143"""
Grand Theater, Leeds, balcony0.142"""
Prince's Theater, Manchester, balcony0.11-0.17"""

(Analyses made by Drs. Smith, Bernays, and De Chaumont.)

Compare with these figures some analyses of the air of sewers. Dr. Russell, of Glasgow, found the air of a well-ventilated and flushed sewer to contain 0.051 vols. of CO2. The late Prof. W. Ripley Nichols conducted many careful experiments on the amount of carbonic acid in the Boston sewers, and found the following averages, viz., 0.087, 0.082, 0.115, 0.107, 0.08, or much less than the above analyses of theater air showed. He states: "It appears from these examinations that the air even in a tide-locked sewer does not differ from the standard as much as many no doubt suppose."

A comparison of the number of bacteria found in a cubic foot of air inside of a theater and in the street air would form a more convincing statement, but I have been unable to find published records of any such bacteriological tests. Nevertheless, we know that while the atmosphere contains some bacteria, the indoor air of crowded assembly halls, laden with floating dust, is particularly rich in living micro-organisms. This has been proved by Tyndall, Miquel, Frankland, and other scientists; and in this connection should be mentioned one point of much importance, ascertained quite recently, namely, that the air of sewers, contrary to expectation, is remarkably free from germs. An analysis of the air in the sewers under the Houses of Parliament, London, showed that the number of micro-organisms was much less than that in the atmosphere outside of the building.

In recent years marked improvements in theater planning and equipment have been effected, and corresponding steps in advance have been made in matters relating to theater hygiene. It should therefore be understood that my remarks are intended to apply to the average theater, and in particular to the older buildings of this class. There are in large cities a few well-ventilated and hygienically improved theaters and opera houses, in which the requirements of sanitation are observed. Later on, when speaking more in detail of theater ventilation, instances of well-ventilated theaters will be mentioned. Nevertheless, the need of urgent and radical measures for comfort and health in the majority of theaters is obvious. Much is being done in our enlightened age to improve the sanitary condition of school buildings, jails and prisons, hospitals and dwelling houses. Why, I ask, should not our theaters receive some consideration?

The efficient ventilation of a theater building is conceded to be an unusually difficult problem. In order to ventilate a theater properly, the causes of noxious odors arising from bad plumbing or defective drainage should be removed; outside fumes or vapors must not be permitted to enter the building either through doors or windows, or through the fresh-air duct of the heating apparatus. The substitution of electric lights in place of gas is a great help toward securing pure air. This being accomplished, a standard of purity of the air should be maintained by proper ventilation. This includes both the removal of the vitiated air and the introduction of pure air from outdoors and the consequent entire change of the air of a hall three or four times per hour. The fresh air brought into the building must be ample in volume; it should be free from contamination, dust and germs (particularly pathogenic microbes), and with this in view must in cities be first purified by filtering, spraying, or washing. It should be warmed in cold weather by passing over hot-water or steam-pipe stacks, and cooled in warm weather by means of ice or the brine of mechanical refrigerating machines. The air should be of a proper degree of humidity, and, what is most important of all, it should be admitted into the various parts of the theater imperceptibly, so as not to cause the sensation of draught; in other words, its velocity at the inlets must be very slight. The fresh air should enter the audience hall at numerous points so well and evenly distributed that the air will be equally diffused throughout the entire horizontal cross-section of the hall. The air indoors should have as nearly as possible the composition of air outdoors, an increase of the CO2 from 0.3 to 0.6 being the permissible limit. The vitiated air should be continuously removed by mechanical means, taking care, however, not to remove a larger volume of air than is introduced from outdoors.

Regarding the amount of fresh outdoor air to be supplied to keep the inside atmosphere at anything like standard purity, authorities differ somewhat. The theoretical amount, 3,000 cubic feet per person per hour (50 cubic feet per minute), is made a requirement in the Boston theater law. In Austria, the law calls for 1,050 cubic feet. The regulations of the Prussian Minister of Public Works call for 700 cubic feet, Professor von Pettenkofer suggests an air supply per person of from 1,410 to 1,675 cubic feet per hour (23 to 28 cubic feet per minute), General Morin calls for 1,200 to 1,500 cubic feet, and Dr. Billings, an American authority, requires 30 cubic feet per minute, or 1,800 cubic feet per hour. In the Vienna Opera House, which is described as one of the best-ventilated theaters in the world, the air supply is 15 cubic feet per person per minute. The Madison Square Theater, in New York, is stated to have an air supply of 25 cubic feet per person.

In a moderately large theater, seating twelve hundred persons, the total hourly quantity of air to be supplied would, accordingly, amount to from 1,440,000 to 2,160,000 cubic feet. It is not an easy matter to arrange the fresh-air conduits of a size sufficient to furnish this volume of air; it is obviously costly to warm such a large quantity of air, and it is a still more difficult problem to introduce it without creating objectionable currents of air; and, finally, inasmuch as this air can not enter the auditorium unless a like amount of vitiated air is removed, the problem includes providing artificial means for the removal of large air volumes.

Where gas illumination is used, each gas flame requires an additional air supply—from 140 to 280 cubic feet, according to General Morin.

A slight consideration of the volumes of air which must be moved and removed in a theater to secure a complete change of air three or four times an hour, demonstrates the impossibility of securing satisfactory results by the so-called natural method of ventilation—i. e., the removal of air by means of flues with currents due either to the aspirating force of the wind or due to artificially increased temperature in the flues. It becomes necessary to adopt mechanical means of ventilation by using either exhaust fans or pressure blowers or both, these being driven either by steam engines or by electric motors. In the older theaters, which were lighted by gas, the heat of the flames could be utilized to a certain extent in creating ascending currents in outlet shafts, and this accomplished some air renewal. But nowadays the central chandelier is almost entirely dispensed with; glowing carbon lamps, fed by electric currents, replace the gas flames; hence mechanical ventilation seems all the more indicated.