Fig. 9.
It will be noticed in the figure that the T stiffeners occur only at the outer face of the web, and that the inner vertical strips stop short at the top edge of the angles, the result being that under load the flange would tend to twist around some point, say A, at each stiffener, inducing a serious stress in the thin web at that place, while away from these stiffeners the web would be more free to yield without tearing. The fact that at a number of the stiffeners incipient cracks were observed, some only a few inches long, suggests this view of the matter.
A case of web-failure from other influences coming under notice showed breaks at the upper part of the web extending downwards.
In this bridge, of 32 feet span, which had been in existence thirty-two years, the webs—originally 1⁄4 inch thick—were, largely because of cinder ballast in contact with them, so badly wasted as to be generally little thicker than a crown-piece, and in places were eaten through; in addition to which, the road being on a sharp curve, the rail-balks had been strutted from the webs to keep them in position, the effect of which would be to exert a hammering thrust upon the face of the web at the abutting ends, and assist in starting cracks in webs already much corroded. A feature of this case, tending to show that the breaks resulted as the joint effect of waste and ill-usage by the strut members, rather than by excessive stress in the web as reduced, is to be found in the fact that the girders when removed were observed to be in remarkably good shape—i.e. the camber, marked on the original drawings to be 11⁄2 inch, still showed as a perfectly even curve of that rise, which would hardly have been the case if the lower flange had been let down by web-rupture, the result of excessive web-stresses.
Occasionally webs will crack through the solid unwasted plate, in a line nearly vertical; not where shear stress is greatest, but generally at some other place, and from no apparent cause, either of stress or ill-usage. The writer has observed this only in the case of small girders not exceeding 2 feet in depth; and, for want of any better reason, attributes these cracks to poor material, coupled with some latent defect. In a bridge having some thirty cross-girders, each 26 feet long, about every other one had a web cracked in this manner after many years’ use.
Web-cracks of the kind first indicated, are perhaps, the most probable source of danger in plate-girders, of any which are likely to occur. The fault is insidious, difficult to detect when first developed, and perhaps not seen at all till the bridge, condemned for some other reason, has the girders freely exposed and brought into broad light. The manner in which old girders are sometimes partly concealed by timberwork, or covered by ballast, makes the detection of these defects an uncertain matter, unless sufficient trouble is occasionally taken to render inspection complete.
The manner in which girders with wasted and fractured webs will still hang together under heavy loading seems to warrant the deduction that, in designing new work, it can hardly be necessary to provide such a considerable amount of web-stiffening as is sometimes seen; experience showing that defects of the web-structure do not commonly occur in the stiffening so frequently as in the plate, and then in the form of cracks.