Figs. 830 and 831.—Symmetrical and unsymmetrical distribution. When a main is supplied by a feeder, the junction of the two, if practicable, is located at the electrical center of the main, as indicated in [fig. 830], so that the distribution is symmetrical, that is, the ampere feet each way from the junction are the same. This is nearly always practicable in surface wiring, and when it is practiced it is only necessary to calculate the wire size for one-half of the main, as the other half is identical. In [fig. 830] there are four lamps on each side of the junction, J; the center of each group is at a distance, M, so that the lamp feet in each half of the main are 5 × M. The lamp feet of the feeder would be 10 × N, N being the distance from the feeder fuse block to the junction, J. In concealed work, however, it does not always happen that a feeder can be made to join a main at its electrical center; when this is not practicable, each end of the main should be figured separately. In [fig. 831], for instance, the main has five lamps on one side and two on the other, and the distances from the junction to the centers of the two groups are at unequal distances S and S'. If the distance S be 14 feet, and the lamps, 16 c. p., the lamp feet in the left hand main equals 5 × 14 = 70, while in the main to the right, taking S' at 10 feet, there are only 2 × 10 = 20 lamp feet. Hence what appears to be one continuous main in this case would have to be treated as two mains, and each part figured separately.

circular mils = I × feet × 21.6 E = amperes × feet × 21.6 "drop" . . . . (5)

The following practical example is given to illustrate the application of the formula just obtained:

EXAMPLE.—What size wire should be used on a 250 volt circuit to transmit a current of 200 amperes a distance of 350 feet to a center of distribution with a loss of three per cent. under full load?

The volts lost or drop is equal to 250 × .03 = 7.5 volts.

PROPERTIES OF COPPER WIRE
Number
of gauge
B. & S.
Diameter
in
mils
Area in
circular
mils
Weight in poundsResistance at 68° Fahr.
1,000 feetmileFeet per
pound
1,000 Feetmile
0000460211,600640.53,3811.561.04893.2583
000409.6167,8005082,6821.969.06170.3258
00364.8133,100402.82,1272.482.07780.4108
0324.9105,500319.51,6873.130.09811.5180
1289.383,690253.31,3373.947.12370.6531
2257.666,370200.91,0624.977.1560.8237
3229.452,630159.3841.16.276.19671.0386
4204.341,740126.4667.47.914.24801.3094
5181.933,100100.2529.09.980.31281.6516
6162.026,25079.46419.512.580.39442.0824
7144.320,82063.02332.715.87.49732.6257
8128.516,51049.98263.920.01.62713.3111
9114.413,09039.63209.225.23.79084.1754
10101.910,38031.13166.031.82.99725.2652
1190.748,23424.93131.640.121.2576.6370
1280.816,53019.77104.450.591.5868.374
1371.965,17815.6882.7963.792.00010.560
1464.084,10712.4365.6380.442.52113.311
1557.073,2579.85852.05101.43.17916.785
1650.822,5837.81841.28127.94.00921.168
1745.262,0486.20032.74161.35.05526.690
1840.301,6244.91725.96203.46.37433.655
1935.891,2883.89920.59256.58.03842.440
2031.961,0223.09216.33323.410.1415.340

Substituting the given value in formula (5)

circular mils = 350 × 200 × 21.6 7.5 = 201,600.

Diameter = 2 √201,600 = 449 circular mils or .449 in.

From the table (on [page 731] or on [page 742]) the nearest (larger) size of wire is 0000 B. & S. gauge.[4]

WIRING TABLE FOR LIGHT AND POWER CIRCUITS
VOLTSPERCENTAGE OF LOSS
20001.71.51.41.21.11.00.750.5
10003.42.92.72.42.22.01.51.0
5006.55.76.24.84.33.92.92.0
22013.712.011.010.39.38.36.54.4
11020.018.517.015.412.08.4
5222.416.1
VOLTSPERCENTAGE OF LOSS (continued)
20000.450.40.350.30.250.20.150.10.05
10000.90.80.70.60.50.40.30.20.1
5001.81.61.41.21.00.80.60.40.2
2203.93.53.12.72.21.81.40.90.45
1107.66.86.05.24.43.52.71.80.9
5214.713.311.810.38.87.15.53.71.9
ACTUAL VOLTS LOST
Carrying
Capacity
Amperes.
Size
B. & S.
353027.52522.5201510
300000034580029640027170024700022230019760014820098800
24500027440023520021560019600017640015680011760078400
215002175251864501709121553751398371243009322562150
1900172550147900135575123250110925986007395049300
16011368501173001075259775087975782005865039100
135210850093000852507750069750620004650031000
11538610073800676506150055350492003690024600
10046825058500536254875043875390002925019500
9055425046500426253875034875310002325015500
8064305036900338253075027675246001845012300
608269652313021202192751734715420115657710
40101697514550133371212510912970072754850
3012106759150838876256862610045753050
221467205760528048004320384028801920
5[5]1642353630332830252723242018151210
ACTUAL VOLTS LOST (continued)
Carrying
Capacity
Amperes.
Size
B. & S.
987654321
300000088920790406916059280494003952029640197609880
24500070560627205488047040392003136023520156807840
2150055935497204350537290310752486018645124306215
19004437039440345102958024650197201479098604930
160135190312802737023460195501564011730 78203910
1352279002480021700186001550012400930062003100
115322140196801722014760123009840738049202460
10041755015600136501170097507800585039001950
905139501240010850930077506200465031001550
8061107098408610738061504920369024601230
60869396168539746263855308423131542771
40104365388033952910242519401455970486
3012274524402135183015251220915610305
22141728153613441152960768576384192
5[5]161089968847726605484363242121

RULE.—Multiply current in amperes by single distance and refer to the nearest corresponding number under column of actual volts lost, to find size of wire. It should also be noted that the underwriters prohibit the use of wire smaller than No. 14 B. & S. gauge, except as allowed for fixture work and pendant cord.